Abstract
The addition of 0.5 MWp of PVDG in the Singosari distribution system for the Karangploso feeder located in East Java, Indonesia will have an impact on the existing system. Voltage stability in the system is a major concern to guarantee system safety operations that have an impact on consumers. System analysis using Probability Density Function (PDF) is used to ensure that the voltage profile on the system due to PVDG injection is still within the allowable value. By using the PDF method, the uncertainty from sources originating from solar panels (sources) can be calculated. So, when the distribution system does not get power injection from solar panels, then it can be known whether the system can still work properly or not. In this study it was shown that the voltage profile at each bus has increased, especially on bus 74 which was previously undervoltage with a value of 0.9483 to 0.97.
Original language | English |
---|---|
Article number | 050055 |
Journal | AIP Conference Proceedings |
Volume | 3077 |
Issue number | 1 |
DOIs | |
Publication status | Published - 12 Jul 2024 |
Event | 2022 Transdisciplinary Symposium on Engineering and Technology: Development of Digital and Green Technology on Post Pandemic Era, TSET 2022 - Yogyakarta, Indonesia Duration: 21 Sept 2022 → … |